| Note the elevated temperature (around 60 degrees) of the
central cable on the upper section of the 'Siemens' contactor. A perspex shield prevents a clear view of the area,
but a loose connection is suspected. Advise check security of upper connections on this contactor. |
The temperature of the trip Q 14 is around 100 degrees Celcius.
None of the connecting cables appear to be operating at high temperatures suggesting the fault is internal. |
This image is of the main isolator in an electrical control
panel. Note the elevated temperature (+10 degrees compared to the other phases) of the upper connection 'blue'
phase. The temperature gradient suggests a poor connection. |